12.8 H: Terminal Function Selection
Logical Operation Selection
H2-61, H2-64, H2-67
5
6
7
8
Note:
• If you use the function to output logical calculation results, you cannot set H2-01 to H2-03 = 1xx [Inverse Output of xx]. If you do, the
drive will detect oPE33 [Digital Output Selection Error].
• When you do not use H2-60, H2-63, and H2-66, set them to F. The through mode function is not supported.
◆
H2 MFDO Parameters
■
H2-01: Term MA/MB-MC Function Selection
No.
Name
(Hex.)
H2-01
Term MA/MB-MC
Function Selection
(040B)
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in through mode.
■
H2-02: Term P1-C1 Function Selection
No.
Name
(Hex.)
H2-02
Term P1-C1 Function
Selection
(040C)
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in through mode.
■
H2-03: Term P2-C2 Function Selection
No.
Name
(Hex.)
H2-03
Term P2-C2 Function
Selection
(040D)
Note:
Set this parameter to F when the terminal is not being used or to use the terminal in through mode.
■
H2-06: Watt Hour Output Unit Selection
No.
Name
(Hex.)
H2-06
Watt Hour Output Unit
Selection
(0437)
This output is input to the Watt hour meter or PLC through a 200 ms pulse signal. This parameter sets the kWh
unit for each pulse output.
622
Logical Operation Expression
A != B
AND(A, )
OR(A, )
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function set for MFDO terminal MA-MC or MB-MC.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function for MFDO terminal P1-C1.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function for MFDO terminal P2-C2.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the unit for the output signal when H2-01 to H2-03 = 39 [MFDO Function Selection = Watt
Hour Pulse Output].
-
Description
Description
Description
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Logical Operation Notation
On
Default
(Range)
E
(0 - 1FF)
Default
(Range)
0
(0 - 1FF)
Default
(Range)
2
(0 - 1FF)
Default
(Range)
0
(0 - 4)