O3: Copy Function - YASKAWA FSDrive-MV1000 Parameter Manual

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

1.3 Parameter Table
No.
Name
(Addr.)
o3-01
Copy Function
(515H)
Selection
o3-02
Copy Allowed
(516H)
Selection
Cumulative
o4-01
Operation Time
(50BH)
Setting
Cumulative
o4-02
Operation Time
(50CH)
Selection
o4-11
U2, U3 Initialization
(510H)
o4-12
kWh Monitor
(512H)
Initialization
Number of Run
o4-13
Commands Counter
(528H)
Initialization
o4-20
Event Log
(3090H)
Initialization
o4-21
Trace Initialization
(3091H)
<6> Default setting is determined by o2-04, Drive Model Selection.
<10> Default setting is determined by A1-02, Control Method Selection.
<36> Default setting is determined by o1-03, Frequency Reference Selection/Display Unit Setting.
74

o3: Copy Function

All Modes
0: No action
1: Read parameters from the drive, saving them onto the digital operator.
2: Copy parameters from the digital operator, writing them to the drive.
3: Verify parameter settings on the drive to check if they match the data
saved on the operator.
All Modes
0: Read operation prohibited
1: Read operation allowed
o4: Maintenance Monitor Settings
All Modes
Sets the value for the cumulative operation time of the drive in units of 10 h.
All Modes
0: Logs power-on time
1: Logs operation time when the drive output is active (output operation
time).
All Modes
0: U2-
and U3-
monitor data is not reset when the drive is initialized
(A1-03).
1: U2-
and U3-
monitor data is reset when the drive is initialized
(A1-03).
All Modes
0: U4-10 and U4-11 monitor data is not reset when the drive is initialized
(A1-03).
1: U4-10 and U4-11 monitor data is reset when the drive is initialized
(A1-03).
All Modes
0: Number of Run commands counter is not reset when the drive is
initialized (A1-03).
1: Number of Run commands counter is reset when the drive is initialized
(A1-03).
All Modes
0: Event log data is not reset when the drive is initialized (A1-03).
1: Event log data is reset when the drive is initialized (A1-03).
All Modes
0: Trace data is not reset when the drive is initialized (A1-03).
1: Trace data is reset when the drive is initialized (A1-03).
Description
YASKAWA ELECTRIC TOEP C710687 03B FSDrive-MV1000 Parameter Guide
Setting
common_
Default: 0
Min: 0
Max: 3
Default: 0
common_
Min: 0
Max: 1
Default: 0
common_
Min: 0
Max: 9999
common_
Default: 0
Min: 0
Max: 1
common_
Default: 0
Min: 0
Max: 1
common_
Default: 0
Min: 0
Max: 1
common_
Default: 0
Min: 0
Max: 1
Default: 0
common_
Min: 0
Max: 1
Default: 0
common_
Min: 0
Max: 1
Page
235
236
236
236
236
237
237
237
237