Setting 1: ENTER key not required
The output frequency changes immediately when the reference is changed by the up or down arrow keys on the digital operator.
The ENTER key does not need to be pressed. The frequency reference is saved for 5 s after it is changed.
n
o2-06: Operation Selection when Digital Operator is Disconnected
Determines whether the drive will stop when the digital operator is removed in LOCAL mode or when b1-02 or b1-16 is set
to 0. When the operator is reconnected, the display will indicate that it was disconnected.
No.
o2-06
Setting 0: Continue operation
The operation continues.
Setting 1: Trigger a fault
The operation stops and triggers an oPr fault. The motor coasts to stop.
n
o2-07: Motor Direction at Power Up when Using Operator
Determines the direction the motor will rotate after the drive is powered up and the Run command is given from the digital
operator.
Note: This parameter is effective only when the Run command is set to be given from the digital operator (b1-02, b1-16 = 0).
No.
o2-07
Motor Direction at Power Up when Using Operator
Setting 0: Forward
Setting 1: Reverse
u

o3: Copy Function

These parameters control the Copy function of the digital operator. The Copy function stores parameter settings into the
memory of the digital operator to facilitate the transfer of those settings to other drives that are the same model, capacity, and
same control mode setting.
n
o3-01 Copy Function Selection
Instructs the drive to Read, Write, or Verify parameter settings.
No.
o3-01
Setting 0: Copy Select (no function)
Setting 1: INV --> OP READ
Copies all parameters from the drive to the digital operator.
Note: The copy protection for the digital operator is enabled by default. Set o3-01 to 1 to unlock copy protection, .
Setting 2: OP --> INV WRITE
Copies all parameters from the digital operator to the drive.
Setting 3: OP<-->INV VERIFY
Compares the parameters in the drive with the parameter settings saved on the digital operator to see if they match.
n
o3-02 Copy Allowed Selection
Allows and restricts the use of the Copy function.
No.
o3-02
Setting 0: Disabled
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Name
Digital Operator Disconnection Operation
Name
Refer to Copy Function Related Displays on page 332
Name
Copy Function Selection
Name
Copy Allowed Selection
5.10 o: Operator Related Settings
Setting Range
0, 1
Setting Range
0, 1
for a description of errors and displays.
Setting Range
0 to 3
Setting Range
0, 1
Default
0
Default
0
Default
0
5
Default
0