F6: Communication Option Card - YASKAWA T1000V Technical Manual

Ac drive for textile applications
Table of Contents

Advertisement

F1-10, F1-11: Excessive Speed Deviation Detection Level, Delay Time
F1-10 sets the detection level for a speed deviation (dEv) fault as a percentage of the maximum output frequency. The
speed feedback has to exceed this level for longer than the time set in F1-11 before a fault is detected. Speed deviation is
the difference between actual motor speed and the frequency reference command.
No.
F1-10
F1-11
Excessive Speed Deviation Detection Delay Time
F1-14: PG Open-Circuit Detection Time
Sets the time required to detect PGo if no pulse signal is present at terminal RP.
No.
F1-14

◆ F6: Communication Option Card

These parameters are to configure communication option cards and communication fault detection methods.
F6-01: Communications Error Operation Selection
Determines drive operation if a communication error occurs.
No.
F6-01
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast-stop Using C1-09
Setting 3: Alarm Only, Continue Operation
F6-02: External Fault from Comm. Option Detection Selection
Determines the detection method of an external fault initiated by a communication option (EF0).
No.
F6-02
External Fault from Comm. Option Detection Selection
Setting 0: Always Detected
Setting 1: Detection During Run Only
F6-03: External Fault from Comm. Option Operation Selection
Determines the operation when an external fault is initiated by a communication option (EF0).
No.
F6-03
External Fault from Comm. Option Operation Selection
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast-stop Using C1-09
Setting 3: Alarm Only, Continue Operation
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Parameter Name
Excessive Speed Deviation Detection Level
Parameter Name
PG Open-Circuit Detection Time
Parameter Name
Communications Error Operation Selection
Parameter Name
Parameter Name
5.6 F: Option Settings
Setting Range
0 to 50%
0.0 to 10.0 s
Setting Range
0.0 to 10.0 s
Setting Range
0 to 3
Setting Range
0 or 1
Setting Range
0 to 3
Default
10%
0.5 s
Default
2.0 s
Default
1
Default
0
5
Default
1
157