Siemens G130 List Manual page 580

Hide thumbs Also See for G130:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Dependency:
Refer to: p2000
Note:
This BICO parameter provides the numerical value of the reference quantity p2000 as a connector output for
interconnection with Drive Control Chart (DCC). The numerical value can be adopted unchanged from this connector
output in DCC.
This BICO parameter is not suitable for interconnecting for cyclic communication.
r2700
CO: Reference frequency / f_ref
B_INF
Can be changed: -
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-
Description:
Display and connector output of the actual reference quantity for the frequency (p2000).
All frequencies specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
This parameter has the unit Hz.
Dependency:
Refer to: p2000
Note:
This BICO parameter provides the numerical value of the reference quantity p2000 as a connector output for
interconnection with Drive Control Chart (DCC). The numerical value can be adopted unchanged from this connector
output in DCC.
This BICO parameter is not suitable for interconnecting for cyclic communication.
r2700
CO: Reference velocity/reference frequency actual / v_ref/f_ref act
ENC (Lin_enc)
Can be changed: -
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-
Description:
Display and connector output for the actual reference quantity for velocity and frequency.
All velocities or frequencies specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
The following applies:
Reference frequency (in Hz) = reference velocity (in m/min) / 60
Dependency:
Refer to: p2000
Note:
This BICO parameter provides the numerical value of the reference quantity p2000 as a connector output for
interconnection with Drive Control Chart (DCC). The numerical value can be adopted unchanged from this connector
output in DCC.
This BICO parameter is not suitable for interconnecting for cyclic communication.
r2701
CO: Reference voltage / Reference voltage
VECTOR_G, B_INF
Can be changed: -
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-
Description:
Connector output of the reference quantity for voltages p2001.
All voltages specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
This parameter has the unit Vrms.
Dependency:
Refer to: p2001
580
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents