r0565[0...15]
CO: Probe time stamp / Probe t_stamp
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: Unsigned16
CU_G130_DP,
P-Group: Displays, signals
CU_G150_DP
Not for motor type: -
Min
-
Description:
Display and connector output for the time stamp MT_ZS_1 up to MT_ZS_16.
Displays the measuring time for an edge at the digital input for the "central measuring probe evaluation stage 3"
function.
The measuring time is specified as 16-bit value with a resolution of 0.25 µs.
Priority:
MT1 ... MT8, oldest ... newest time stamp
r0566[0...3]
CO: Probe time stamp reference / Probe t_stamp name
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: Unsigned16
CU_G130_DP,
P-Group: Displays, signals
CU_G150_DP
Not for motor type: -
Min
-
Description:
Display and connector output for the time stamp reference MT_ZSB1 up to MT_ZSB4.
r0567
CO: Probe diagnostics word / Probe diag_word
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: Unsigned16
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
-
Description:
Display and connector output for diagnostics word MT_DIAG.
p0570
Inhibit list values effective number / Inhib list no
VECTOR_G
Can be changed: U, T
Data type: Unsigned8
P-Group: Applications
Not for motor type: -
Min
0
Description:
Sets the number of parameters in the inhibit list p0571.
This number of parameters can be automatically excluded from the calculation of the motor and control parameters
(see p0340, p0578), starting from index 0.
Note:
Defines the number of entries in p0571 that should be taken into account.
The inhibit list is deactivated for a value of 0.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
50
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0