Note:
This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
DI/DO: Bidirectional Digital Input/Output
p4095
TB30 digital inputs simulation mode / TB30 DI sim_mode
TB30
Can be changed: U, T
Data type: Unsigned32
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the simulation mode for the digital inputs of the Terminal Board 30 (TB30).
Bit field:
Bit
00
01
02
03
Dependency:
The setpoint for the input signals is specified using p4096.
Refer to: p4096
Warning:
A drive that is moved by simulating the inputs of a Terminal Board is brought to a standstill while the Terminal Module
is being activated or deactivated.
Note:
This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
p4096
TM31 digital inputs simulation mode setpoint / TM31 DI sim setp
TM31
Can be changed: U, T
Data type: Unsigned32
P-Group: Terminals
Not for motor type: -
Min
-
Description:
Sets the setpoint for the input signals in the simulation mode of the digital inputs of Terminal Module 31 (TM31).
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
11
Dependency:
The simulation of a digital input is selected using p4095.
Refer to: p4095
Note:
This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
DI/DO: Bidirectional Digital Input/Output
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
DI 0 (X481.1)
DI 1 (X481.2)
DI 2 (X481.3)
DI 3 (X481.4)
Signal name
DI 0 (X520.1)
DI 1 (X520.2)
DI 2 (X520.3)
DI 3 (X520.4)
DI 4 (X530.1)
DI 5 (X530.2)
DI 6 (X530.3)
DI 7 (X530.4)
DI/DO 8 (X541.2)
DI/DO 9 (X541.3)
DI/DO 10 (X541.4)
DI/DO 11 (X541.5)
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Simulation
Simulation
Simulation
Simulation
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
High
High
High
High
High
High
High
High
High
High
High
High
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 9099, 9100
Unit selection: -
Expert list: 1
Factory setting
0000 bin
0 signal
Terminal eval
Terminal eval
Terminal eval
Terminal eval
Access level: 2
Func. diagram: 9549, 9550,
9552, 9560, 9562
Unit selection: -
Expert list: 1
Factory setting
0000 0000 0000 0000 bin
0 signal
Low
Low
Low
Low
Low
Low
Low
Low
Low
Low
Low
Low
FP
-
-
-
-