p2201[0...n]
CO: Technology controller fixed value 1 / Tec_ctrl fix val1
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-200.00 [%]
Description:
Sets the value for fixed value 1 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2202[0...n]
CO: Technology controller fixed value 2 / Tec_ctr fix val 2
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-200.00 [%]
Description:
Sets the value for fixed value 2 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2203[0...n]
CO: Technology controller fixed value 3 / Tec_ctr fix val 3
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-200.00 [%]
Description:
Sets the value for fixed value 3 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2204[0...n]
CO: Technology controller fixed value 4 / Tec_ctr fix val 4
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-200.00 [%]
Description:
Sets the value for fixed value 4 of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222, p2223, r2224, r2229
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
562
Calculated: -
Dyn. index: DDS, p0180
Unit group: 9_1
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: 9_1
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: 9_1
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: 9_1
Scaling: PERCENT
Max
200.00 [%]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: 7950, 7951
Unit selection: p0595
Expert list: 1
Factory setting
10.00 [%]
Access level: 2
Func. diagram: 7950, 7951
Unit selection: p0595
Expert list: 1
Factory setting
20.00 [%]
Access level: 2
Func. diagram: 7950, 7951
Unit selection: p0595
Expert list: 1
Factory setting
30.00 [%]
Access level: 2
Func. diagram: 7950, 7951
Unit selection: p0595
Expert list: 1
Factory setting
40.00 [%]