2 Parameters
2.2 List of parameters
p0922
IF1 PROFIdrive PZD telegram selection / IF1 PZD telegr
CU_G130_PN,
Can be changed: C2(1), T
CU_G150_PN,
Data type: Unsigned16
CU_G130_DP,
CU_G150_DP
P-Group: Communications
Not for motor type: -
Min
390
Description:
Sets the send and receive telegram.
Value:
390:
391:
392:
393:
394:
395:
999:
p0922
IF1 PROFIdrive PZD telegram selection / IF1 PZD telegr
VECTOR_G
Can be changed: C2(1), T
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
1
Description:
Sets the send and receive telegram.
Value:
1:
2:
20:
220:
352:
999:
Caution:
Telegrams 2, 3 and 4 are not suitable for sensorless vector control (p1300 = 20). For sensorless vector control, it is
necessary that the setpoint speed is entered at the ramp-function generator input (e.g. p1070) and not after the
ramp-function generator (p1155).
Note:
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are
inhibited. The inhibited interconnections can only be changed again after setting value 999.
p0922
IF1 PROFIdrive PZD telegram selection / IF1 PZD telegr
VECTOR_G (n/M)
Can be changed: C2(1), T
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
1
Description:
Sets the send and receive telegram.
Value:
1:
2:
3:
4:
20:
220:
352:
999:
290
SIEMENS telegram 390, PZD-2/2
SIEMENS telegram 391, PZD-3/7
SIEMENS telegram 392, PZD-3/15
SIEMENS telegram 393, PZD-4/21
SIEMENS telegram 394, PZD-3/3
SIEMENS telegram 395, PZD-4/25
Free telegram configuration with BICO
Standard telegram 1, PZD-2/2
Standard telegram 2, PZD-4/4
Standard telegram 20, PZD-2/6
SIEMENS telegram 220, PZD-10/10
SIEMENS telegram 352, PZD-6/6
Free telegram configuration with BICO
Standard telegram 1, PZD-2/2
Standard telegram 2, PZD-4/4
Standard telegram 3, PZD-5/9
Standard telegram 4, PZD-6/14
Standard telegram 20, PZD-2/6
SIEMENS telegram 220, PZD-10/10
SIEMENS telegram 352, PZD-6/6
Free telegram configuration with BICO
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
999
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
999
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
999
List Manual (LH2), 07/2016, A5E03263479A
Access level: 1
Func. diagram: 2401, 2420,
2423, 2481, 2483
Unit selection: -
Expert list: 1
Factory setting
999
Access level: 1
Func. diagram: 2401, 2415,
2416, 2419, 2420, 2421, 2422,
2423
Unit selection: -
Expert list: 1
Factory setting
999
Access level: 1
Func. diagram: 2401, 2415,
2416, 2419, 2420, 2421, 2422,
2423
Unit selection: -
Expert list: 1
Factory setting
999