2 Parameters
2.2 List of parameters
p3900
Completion of quick commissioning / Compl quick_comm
B_INF
Can be changed: C2(1)
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Exits the quick commissioning (p0010 = 1) with automatic calculation of all of the parameters that depend on the
entries made during the quick commissioning.
p3900 = 1 initially includes a parameter reset (factory setting, the same as p0970 = 1) for all parameters of the drive
object; however, without overwriting the entries made during the quick commissioning. The interconnections of
PROFIBUS PZD telegram selection (p0922) and the interconnections via p0700 are re-established and all of the
dependent filter and closed-loop control parameters are calculated (corresponding to p0340 = 1).
p3900 = 2 includes the restoration of the interconnections of PROFIBUS PZD telegram selection (p0922) and the
interconnections via p0700 and the calculations corresponding to p0340 = 1.
p3900 = 3 only includes the end of quick commissioning.
Value:
0:
1:
2:
3:
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
When the calculations have been completed, p3900 and p0010 are automatically reset to a value of zero.
p3901[0...n]
Power unit EEPROM Vdc offset calibration / PU EEPROM Vdc offs
VECTOR_G, B_INF
Can be changed: C1, C2(1), T
Data type: FloatingPoint32
P-Group: All groups
Not for motor type: -
Min
-40.0 [V]
Description:
Differential voltage for calibrating the offset for DC link voltage measurement.
Dependency:
Refer to: r0192, p0212
Caution:
Incorrect use of the calibration can have a negative impact on the closed-loop control.
The parameter influences the upper and lower voltage detection.
Note:
Parameter entries are directly saved in the DRIVE-CLiQ component involved.
The parameter is only effective in the case of booksize power units, if r0192.22 = 1 and p0212.0 = 1.
r3925[0...n]
Identification final display / Ident final_disp
VECTOR_G
Can be changed: -
Data type: Unsigned32
P-Group: Motor
Not for motor type: -
Min
-
Description:
Displays the commissioning steps that have been carried out.
Bit field:
Bit
00
02
03
04
634
No quick parameterization
Quick parameterization after parameter reset
Quick param. (only) for controller par. and reset for BICO par
Completion of quick commissioning
Signal name
Motor/control parameters calculated (p0340
= 1, p3900 > 0)
Motor data identification carried out at
standstill (p1910 = 1)
Rotating measurement carried out (p1960 =
1, 2)
Motor encoder adjustment carried out
(p1960 = 1, p1990 = 1, 3)
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3
Calculated: -
Dyn. index: PDS, p0120
Unit group: -
Scaling: -
Max
40.0 [V]
Calculated: CALC_MOD_ALL
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
List Manual (LH2), 07/2016, A5E03263479A
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.0 [V]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
SINAMICS G130/G150