Siemens G130 List Manual page 1057

Hide thumbs Also See for G130:
Table of Contents

Advertisement

r10053.0...3
CO/BO: SI TM54F digital inputs 20 ... 23 status / SI DI 20...23 stat
TM54F_SL
Can be changed: -
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Displays the status of the digital inputs at the Terminal Module 54F (TM54F).
Bit field:
Bit
00
01
02
03
r10054
SI TM54F failsafe events active / SI failsafe act
TM54F_MA,
Can be changed: -
TM54F_SL
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Displays the events that lead to the transfer of failsafe signals to all drives assigned to the TM54F.
If the second channel of the TM54F transmits failsafe signals, then these are synchronized to the other channel. In
this particular case, p10054 of the other TM54F channel should be evaluated.
Possibilities of resolving the situation:
- error during test stop: correctly perform the test stop.
- internal software error: no possibility of resolving this problem, POWER ON.
- internal synchronization problem: no possibility of resolving this problem, POWER ON.
- internal status error: no possibility of resolving this problem, POWER ON.
- parameterizing error: evaluate fault F35004 or F35006. Resolve parameterizing error. POWER ON. After the
TM54F firmware has been updated, a POWER ON may be required.
- all other causes: remove the cause of the error and carry out a safe acknowledgment (p10006).
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
31
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
DI 20
DI 21
DI 22
DI 23
Signal name
Commissioning mode active (p0010 = 95)
Checksum error of the safety parameters
Synchronization problem within TM54F
Internal software error
Overvoltage in the TM54F
Undervoltage in the TM54F
Error at test stop
Error for crosswise data comparison within
TM54F
Overtemperature in the TM54F
Internal state error
Param error
Failsafe events active on another channel
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
High
High
High
High
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 2892
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
Low
Low
Low
Low
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
No
No
No
FP
2895
2895
2895
2895
FP
2891
-
-
-
-
-
-
-
-
-
-
-
1057