2 Parameters
2.2 List of parameters
p8945
CBE2x interface configuration / CBE2x int config
CU_G130_PN (PN
Can be changed: U, T
CBE20),
Data type: Integer16
CU_G150_PN (PN
P-Group: -
CBE20),
Not for motor type: -
CU_G130_DP (PN
CBE20),
Min
CU_G150_DP (PN
0
CBE20)
Description:
Sets the activation of the interface configuration for the Communication Board Ethernet 20/25 (CBE20/CBE25).
p8945 is automatically set to 0 at the end of an operation.
Value:
0:
2:
3:
Dependency:
Refer to: p8940, p8941, p8942, p8943, p8944
Refer to: A08565
Notice:
When the DHCP mode is active (p8944 > 0), then PROFINET communication via this interface is no longer possible!
However, the interface can be used by the STARTER/SCOUT commissioning tool.
Note:
For CBE20, the parameter is only valid for firmware version "PROFINET Device" (p8835 = 1), "EtherNet/IP" (p8835 =
4) or "MODBUS TCP (p8835 = 5). Otherwise, it is locked.
This restriction is not applicable for the CBE25.
When a project is downloaded, the interface configuration is only activated if, in the offline project, parameter p8945
is set = 2.
For p8945 = 2:
The interface configuration (p8940 and following) is saved and activated after the next POWER ON.
For p8945 = 3:
The factory setting of the interface configuration is loaded after the next POWER ON.
r8950[0...239]
CBE2x Name of Station actual / CBE2x Name act
CU_G130_PN (PN
Can be changed: -
CBE20),
Data type: Unsigned8
CU_G150_PN (PN
P-Group: -
CBE20),
Not for motor type: -
CU_G130_DP (PN
CBE20),
Min
CU_G150_DP (PN
-
CBE20)
Description:
Displays the actual station name for the Communication Board Ethernet 20/25 (CBE20/CBE25).
r8951[0...3]
CBE2x IP Address actual / CBE2x IP addr
CU_G130_PN (PN
Can be changed: -
CBE20),
Data type: Unsigned8
CU_G150_PN (PN
P-Group: -
CBE20),
Not for motor type: -
CU_G130_DP (PN
CBE20),
Min
CU_G150_DP (PN
0
CBE20)
Description:
Displays the actual IP address for the Communication Board Ethernet 20/25 (CBE20/CBE25).
886
No function
Save and activate configuration
Delete configuration
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
255
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-