Siemens G130 List Manual page 561

Hide thumbs Also See for G130:
Table of Contents

Advertisement

Note:
For bit 10:
The torque threshold value 1 is set in p2174.
For bit 12:
This bit is reset after the fault cause disappears, even if the fault itself is still present.
r2199.0...14
CO/BO: Status word monitoring 3 / ZSW monitor 3
VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
Display and BICO output for the third status word of the monitoring functions.
Bit field:
Bit
00
01
04
05
06
07
11
12
13
14
Dependency:
Refer to: A07823, F07824, F07913
Note:
SESM: separately excited synchronous motor
For bit 00:
The speed threshold value 3 is set in p2161.
For bit 01:
The comparison value is set in p2141. We recommend setting the hysteresis (p2142) for canceling the bit to a value
lower than that in p2141. Otherwise, the bit is not reset.
For bit 11:
The torque threshold value 2 is set in p2194.
For bit 13:
The I2t monitoring detects when the alarm threshold is exceeded (p3243), outputs fault A07823 and sets the status
bit.
For bit 14:
The I2t monitoring detects when the fault threshold is exceeded (100 %), outputs fault A07824 and sets the status bit.
p2200[0...n]
BI: Technology controller enable / Tec_ctrl enable
VECTOR_G
Can be changed: T
(Tech_ctrl)
Data type: Unsigned32 / Binary
P-Group: Technology
Not for motor type: -
Min
-
Description:
Sets the signal source to switch in/switch out the technology controller.
The technology controller is switched in with a 1 signal.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
|n_act| < speed threshold value 3
f or n comparison value reached or
exceeded
Speed setp - act val deviation in tolerance
t_on
Ramp-up/ramp-down completed
Current below the zero current threshold
Speed deviation model/external intolerance Yes
Torque utilization < torque threshold value 2 Yes
Excitation current outside the tolerance
range
I2t alarm threshold exceeded (nur SESM)
I2t fault threshold exceeded (nur SESM)
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 2537
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
No
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0
FP
8010
8010
8011
8011
8020
8012
8012
8020
8022
8022
561