2 Parameters
2.2 List of parameters
p2108[0...n]
BI: External fault 3 / External fault 3
VECTOR_G, B_INF
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Messages
Not for motor type: -
Min
-
Description:
Sets the signal source for external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency:
Refer to: p3110, p3111, p3112
Refer to: F07862
Note:
An external fault is triggered with a 0 signal.
If this fault is output at the Control Unit, then it is transferred to all existing drive objects.
r2109[0...63]
Fault time removed in milliseconds / t_flt resolved ms
All objects
Can be changed: -
Data type: Unsigned32
P-Group: Messages
Not for motor type: -
Min
- [ms]
Description:
Displays the system runtime in milliseconds when the fault was removed.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2114, r2130, r2133, r2136, r3115, r3120, r3122
Notice:
The time comprises r2136 (days) and r2109 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
r2110[0...63]
Alarm number / Alarm number
All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
This parameter is identical to r2122.
p2111
Alarm counter / Alarm counter
All objects
Can be changed: U, T
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
0
Description:
Number of alarms that have occurred after the last reset.
Dependency:
When p2111 is set to 0, the following is initiated:
- all of the alarms of the alarm buffer that have gone [0...7] are transferred into the alarm history [8...63].
- the alarm buffer [0...7] is deleted.
Refer to: r2110, r2122, r2123, r2124, r2125
Note:
The parameter is reset to 0 at POWER ON.
540
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
65535
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 2546
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 8050, 8060
Unit selection: -
Expert list: 1
Factory setting
- [ms]
Access level: 2
Func. diagram: 8065
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 8050, 8065
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents