r9976[0...7]
System utilization / Sys util
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
- [%]
Description:
Displays the system utilization.
If the utilization is greater than 100%, fault F01054 is output.
Index:
[0] = Reserved
[1] = Computing time utilization
[2] = Reserved
[3] = Reserved
[4] = Reserved
[5] = Largest total utilization
[6] = Reserved
[7] = Reserved
Dependency:
Refer to: r9979, r9980
Refer to: F01054, F01205
Note:
For index 1:
The value shows the total computing time load of the system.
For index 5:
The total utilization is determined using all sampling times used. The largest total utilization is mapped here. The
sampling time with the largest total utilization is displayed in r9979.
Total utilization:
Computing time load of sampling time involved including load from higher-priority sampling times (interrupts).
r9979
Sampling time with largest total utilization / t_sampl lg total
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
- [µs]
Description:
Displays the sampling time with the largest total utilization.
Dependency:
Refer to: r7901, r9976
Refer to: F01054
Note:
The largest total utilization is displayed in r9976[5].
Total utilization:
Computing time load of sampling time involved including load from higher-priority sampling times (interrupts).
r9980[0...165]
Sampling times utilization calculated / t_sampl util calc
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
- [%]
Description:
Displays the calculated utilizations for the active sampling times based on the existing target topology.
Index:
[0] = Net utilization 0
[1] = Total utilization 0
[2] = Net utilization 1
[3] = Total utilization 1
[4] = Net utilization 2
[5] = Total utilization 2
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [µs]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [%]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [%]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [µs]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [%]
1025