p2035
Fieldbus interface USS PIV drive object number / Fieldbus USS DO_no
CU_G130_DP,
Can be changed: U, T
CU_G150_DP
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
1
Description:
Sets the drive object number for communication via the field bus interface (USS).
Dependency:
Refer to: p0978
Note:
p2035 defines the destination for USS parameter requests (PIV).
p0978[0] defines the destination for USS process data (PZD).
The parameter is available globally on all drive objects.
The parameter is not influenced by setting the factory setting.
p2037
IF1 PROFIdrive STW1.10 = 0 mode / IF1 PD STW1.10=0
VECTOR_G, B_INF,
Can be changed: T
ENC
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
0
Description:
Sets the processing mode for PROFIdrive STW1.10 "master control by PLC".
Generally, control world 1 is received with the first receive word (PZD1) (this is in conformance to the PROFIdrive
profile). The behavior of STW1.10 = 0 corresponds to that of the PROFIdrive profile. For other applications that
deviate from this, the behavior can be adapted using this particular parameter.
Value:
0:
1:
2:
Recommendation:
Do not change the setting p2037 = 0.
Note:
If the STW1 is not transferred according to the PROFIdrive with PZD1 (with bit 10 "master control by PLC"), then
p2037 should be set to 2.
p2038
IF1 PROFIdrive STW/ZSW interface mode / PD STW/ZSW IF mode
VECTOR_G
Can be changed: T
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
0
Description:
Displays the interface mode of the PROFIdrive control words and status words.
Value:
0:
1:
2:
Dependency:
Refer to: p0922, p2079
Notice:
The parameter is protected and cannot be changed.
Note:
For telegram selection p0922 (p2079) = 20, then p2038 is automatically set = 2.
When another telegram is selected, then p2038 is automatically set = 0.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Freeze setpoints and continue to process sign-of-life
Freeze setpoints and sign-of-life
Do not freeze setpoints
SINAMICS
SIMODRIVE 611 universal
VIK-NAMUR
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
62
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
2
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0