p1228
Pulse suppression delay time / Pulse suppr t_del
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
0.000 [s]
Description:
Sets the delay time for pulse suppression.
After OFF1 or OFF3, the pulses are canceled, if at least one of the following conditions is fulfilled:
- the speed actual value falls below the threshold in p1226 and the time started after this in p1228 has expired.
- the speed setpoint falls below the threshold in p1226 and the time started after this in p1227 has expired.
Dependency:
Refer to: p1226, p1227
Notice:
When the motor holding brake is activated, pulse cancellation is additionally delayed by the brake closing time
(p1217).
r1229.1...11
CO/BO: Motor holding brake status word / Brake ZSW
VECTOR_G (Ext
Can be changed: -
brake)
Data type: Unsigned32
P-Group: Functions
Not for motor type: -
Min
-
Description:
Displays the status word for the motor holding brake.
Bit field:
Bit
01
03
04
05
06
07
08
09
10
11
p1230[0...n]
BI: Armature short-circuit / DC braking activation / ASC/DCBRK act
VECTOR_G
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Functions
Not for motor type: -
Min
-
Description:
Sets the signal source to activate the armature short-circuit or DC braking.
Dependency:
Refer to: p1231, p1232, p1233, p1234, p1235, p1236, p1237, r1238, r1239, p1345, p1346
Note:
1 signal: Armature short-circuit/DC braking activated.
0 signal: Armature short-circuit/DC braking deactivated.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
Command open brake (continuous signal)
Pulse enable extended brake control
Brake does not open
Brake does not close
Brake threshold exceeded
Brake threshold undershot
Brake monitoring time expired
Pulse enable request missing/n_ctrl
inhibited
Brake OR logic operation result
Brake AND logic operation result
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
299.000 [s]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 2701, 2704
Unit selection: -
Expert list: 1
Factory setting
0.000 [s]
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
No
Access level: 1
Func. diagram: 7014, 7016,
7017
Unit selection: -
Expert list: 1
Factory setting
0
FP
2711
2711
2711
2711
2707
2704
2704
2707
2707
2707
349

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents