p7011
Par_circuit DC link voltage asymmetry alarm threshold / Vdc_dissym A thrsh
VECTOR_G (Parallel),
Can be changed: U, T
B_INF (Parallel)
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
2 [%]
Description:
Sets the alarm threshold to detect asymmetry of the DC link voltages in the parallel circuit configuration.
The deviation between the measured values and average value is evaluated.
The specified value is referred to the rated link voltage.
Dependency:
Refer to: A05053
p7015
Par_circuit holding brake power unit data set / Brake PDS
VECTOR_G (Parallel) Can be changed: T
Data type: Integer16
P-Group: Converter
Not for motor type: -
Min
0
Description:
Sets the power unit data set for a parallel connection via which the holding brake is controlled.
Value:
0:
1:
2:
3:
4:
5:
6:
7:
99:
Dependency:
Refer to: p0120, p0121
Note:
PDS: Power unit Data Set
Example:
3 power units are connected in parallel and the holding brake is connected to power unit 1.
p0120 = 3
p0121[0] = component number of power unit 0
p0121[1] = component number of power unit 1 (with holding brake)
p0121[2] = component number of power unit 2
--> p7015 = 1
r7020[0...n]
CO: Par_circuit deviation current in phase U / Phase U curr dev
VECTOR_G (Parallel) Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [A]
Description:
Displays the deviation between the measured current actual value of phase U and the average value as peak value.
The maximum deviation from the average value is displayed in r7025.
Dependency:
Refer to: r7021, r7022, r7025
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Power unit data set 0
Power unit data set 1
Power unit data set 2
Power unit data set 3
Power unit data set 4
Power unit data set 5
Power unit data set 6
Power unit data set 7
No holding brake connected
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
100 [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
99
Calculated: -
Dyn. index: PDS, p0120
Unit group: 6_5
Scaling: p2002
Max
- [A]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
10 [%]
Access level: 3
Func. diagram: 2701, 2814
Unit selection: -
Expert list: 1
Factory setting
99
Access level: 3
Func. diagram: -
Unit selection: p0505
Expert list: 1
Factory setting
- [A]