r7027
CO: Par_circuit max. deviation currents phase W / Phase W Max i_dev
VECTOR_G (Parallel) Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [A]
Description:
Displays the maximum absolute deviation of the measured current actual values of phase W from the average value
as peak value.
The deviation of the individual currents from the average value is displayed in r7022.
Dependency:
Refer to: r7022, r7025, r7026
Refer to: A05052
r7030[0...n]
CO: Par_circuit DC link voltage deviation / Vdc deviation
VECTOR_G (Parallel),
Can be changed: -
B_INF (Parallel)
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [V]
Description:
Displays the deviation of the measured DC link voltage from the average value.
The maximum deviation from the average value is displayed in r7031.
Dependency:
Refer to: r7031
r7031
CO: Par_circuit DC link voltage maximum deviation / Vdc deviation max.
VECTOR_G (Parallel),
Can be changed: -
B_INF (Parallel)
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [V]
Description:
Displays the maximum absolute deviation of the measured DC link voltage from the average value.
The deviation of the individual voltages from the average value is displayed in r7030.
Dependency:
Refer to: r7030
Refer to: A05053
p7035[0...n]
Par_circuit circulating current control operating mode / I_cct_ctrl mode
VECTOR_G (Parallel) Can be changed: U, T
Data type: Integer16
P-Group: Modulation
Not for motor type: -
Min
0
Description:
Sets the operating mode of the circulating current control.
The circulating current control ensures symmetrical distribution of the total currents to the individual converters.
Value:
0:
1:
Dependency:
Circulating current control is not possible for separate, offset motor winding systems (p7003 = 2).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Circulating current control deactivated
Circulating current control activated
Calculated: -
Dyn. index: -
Unit group: 6_5
Scaling: p2002
Max
- [A]
Calculated: -
Dyn. index: PDS, p0120
Unit group: -
Scaling: p2001
Max
- [V]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2001
Max
- [V]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: p0505
Expert list: 1
Factory setting
- [A]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [V]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [V]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
755