Siemens G130 List Manual page 249

Hide thumbs Also See for G130:
Table of Contents

Advertisement

Notice:
Regarding the terminal designation:
The first designation is valid for CU320, the second for CU310.
To select the values:
For CX32, NX10 and NX15, only DI/DO 8, 9, 10, 11 can be selected as fast inputs (refer to the Equipment Manual).
Note:
DI/DO: Bidirectional Digital Input/Output
Prerequisite: The DI/DO must be set as input (p0728.x = 0).
If a parameter change is rejected, a check should be performed as to whether the input terminal is already being
used in p0488, p0489, p0493, p0494, p0495, p0580, p2517 or p2518.
p0681
BI: Central measuring probe synchronizing signal signal source / Cen meas sync_sig
CU_G130_PN,
Can be changed: T
CU_G150_PN,
Data type: Unsigned32 / Binary
CU_G130_DP,
P-Group: Commands
CU_G150_DP
Not for motor type: -
Min
-
Description:
Sets the signal source for the synchronizing signal (SYN) of the function "central measuring probe evaluation".
The signal is used to synchronize the common system time between the master and slave.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0682
CI: Central measuring probe control word signal source / Cen meas STW S_src
CU_G130_PN,
Can be changed: T
CU_G150_PN,
Data type: Unsigned32 / Integer16
CU_G130_DP,
P-Group: Displays, signals
CU_G150_DP
Not for motor type: -
Min
-
Description:
Sets the signal source for the control word of the function "central measuring probe evaluation".
p0684
Central measuring probe evaluation technique / Cen meas eval_tech
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: Encoder
CU_G150_DP
Not for motor type: -
Min
0
Description:
Sets the evaluation technique for the "central measuring probe evaluation" function.
Value:
0:
1:
16:
Notice:
For p0684 = 16:
This evaluation procedure is only activated after parameter save and POWER ON.
Note:
During measurement without a handshake, the probe may have a higher evaluation frequency.
The setting "Measurement without handshake" must be supported by the higher-level control. This setting cannot be
used for SIMOTION D with integrated SINAMICS or with CX32.
For p0684 = 0:
Changing this evaluation procedure to p0684 = 1 is possible in the RUN state.
Changing this evaluation procedure to p0684 = 16 is only activated after parameter save and POWER ON.
Permissible combinations in p0922 are:
p0922 = 391, 392, 393, 394
For p0684 = 1:
Changing this evaluation procedure to p0684 = 0 is possible in the RUN state.
Changing this evaluation procedure to p0684 = 16 is only activated after parameter save and POWER ON.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Measurement with handshake
Measurement without handshake 2 edges
Measurement without handshake more than 2 edges
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
16
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
249

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents