Siemens G130 List Manual page 544

Hide thumbs Also See for G130:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Alarm buffer structure (general principle):
r2122[0], r2124[0], r2123[0], r2125[0] --> alarm 1 (the oldest)
. . .
r2122[7], r2124[7], r2123[7], r2125[7] --> Alarm 8 (the latest)
When the alarm buffer is full, the alarms that have gone are entered into the alarm history:
r2122[8], r2124[8], r2123[8], r2125[8] --> Alarm 1 (the latest)
. . .
r2122[63], r2124[63], r2123[63], r2125[63] --> alarm 56 (the oldest)
r2123[0...63]
Alarm time received in milliseconds / t_alarm recv ms
All objects
Can be changed: -
Data type: Unsigned32
P-Group: Messages
Not for motor type: -
Min
- [ms]
Description:
Displays the system runtime in milliseconds when the alarm occurred.
Dependency:
Refer to: r2110, r2114, r2122, r2124, r2125, r2134, r2145, r2146, r3121, r3123
Notice:
The time comprises r2145 (days) and r2123 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
r2124[0...63]
Alarm value / Alarm value
All objects
Can be changed: -
Data type: Integer32
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays additional information about the active alarm (as integer number).
Dependency:
Refer to: r2110, r2122, r2123, r2125, r2134, r2145, r2146, r3121, r3123
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
r2125[0...63]
Alarm time removed in milliseconds / t_alarm res ms
All objects
Can be changed: -
Data type: Unsigned32
P-Group: Messages
Not for motor type: -
Min
- [ms]
Description:
Displays the system runtime in milliseconds when the alarm was cleared.
Dependency:
Refer to: r2110, r2114, r2122, r2123, r2124, r2134, r2145, r2146, r3121, r3123
Notice:
The time comprises r2146 (days) and r2125 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
544
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [ms]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 8050, 8065
Unit selection: -
Expert list: 1
Factory setting
- [ms]
Access level: 3
Func. diagram: 8050, 8065
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 8050, 8065
Unit selection: -
Expert list: 1
Factory setting
- [ms]
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents