2 Parameters
2.2 List of parameters
Bit field:
Bit
00
01
02
03
Dependency:
Refer to: p0145, p0300
Note:
SMI: SINAMICS Sensor Module Integrated
p0304[0...n]
Rated motor voltage / Mot U_rated
VECTOR_G
Can be changed: C2(1, 3)
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
0 [Vrms]
Description:
Sets the rated motor voltage (rating plate).
Dependency:
Refer to: p0349
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
When the parameter value is entered the connection type of the motor (star-delta) must be taken into account.
p0305[0...n]
Rated motor current / Mot I_rated
VECTOR_G
Can be changed: C2(1, 3)
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
0.00 [Arms]
Description:
Sets the rated motor current (rating plate).
Dependency:
Refer to: p0349
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0305 is changed during quick commissioning (p0010 = 1), then the maximum current p0640 is pre-assigned
accordingly. This is not the case when commissioning the motor (p0010 = 3).
If the rated motor current exceeds twice the maximum drive converter current (r0209), then the maximum current is
reduced due to the current harmonics that increase overproportionally (r0067).
Note:
When the parameter value is entered the connection type of the motor (star-delta) must be taken into account.
p0306[0...n]
Number of motors connected in parallel / Motor qty
VECTOR_G
Can be changed: C2(1, 3)
Data type: Unsigned8
P-Group: Motor
Not for motor type: SESM, RESM
Min
1
Description:
Number of motors that can be operated in parallel using one motor data set.
Depending on the motor number entered, internally an equivalent motor is calculated.
The following should be carefully observed for motors connected in series:
The following rating plate data should only be entered for one motor:
- resistances and inductances: p0350 ... p0361
- currents: p0305, p0320, p0323, p0325, p0329, p0389, p0390, p0391, p0392
- power ratings: p0307
- masses/moments of inertia: p0341, p0344
All other parameters take into account the replacement/equivalent motor (e.g. r0331, r0333).
Recommendation:
For motors connected in parallel, external thermal protection should be provided for each individual motor.
132
Signal name
Motor data set selected
Motor connection type
Windings can be changed
Windings can be changed number
1 signal
MDS1
Delta
Yes
2
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
20000 [Vrms]
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
10000.00 [Arms]
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
50
List Manual (LH2), 07/2016, A5E03263479A
0 signal
MDS0
Star
No
0
Access level: 1
Func. diagram: 6301, 6724
Unit selection: -
Expert list: 1
Factory setting
0 [Vrms]
Access level: 1
Func. diagram: 6301
Unit selection: -
Expert list: 1
Factory setting
0.00 [Arms]
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
SINAMICS G130/G150