Siemens G130 List Manual page 434

Hide thumbs Also See for G130:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p1647
Excitation switch-off delay time / Exc t_off
VECTOR_G (n/M)
Can be changed: T
Data type: FloatingPoint32
P-Group: Commands
Not for motor type: ASM, PMSM, REL
Min
0.0 [s]
Description:
Sets the switch-off delay time to shut down the excitation equipment.
Note:
The delay time starts if, when switching off, r0863.0 = 0.
r1648.0 and r1648.3 are reset at the end of the delay time.
r1648.0...11
CO/BO: Excitation control word / Excitation STW
VECTOR_G (n/M)
Can be changed: -
Data type: Unsigned16
P-Group: Displays, signals
Not for motor type: ASM, PMSM, REL
Min
-
Description:
Displays the control word for the excitation equipment.
Bit field:
Bit
00
01
02
03
07
10
11
Note:
For bit 00:
This bit is set dependent on r0863.0.
r1649.0...8
CO/BO: Excitation status word / Excitation ZSW
VECTOR_G (n/M)
Can be changed: -
Data type: Unsigned16
P-Group: Displays, signals
Not for motor type: ASM, PMSM, REL
Min
-
Description:
Displays the status word of the excitation equipment.
Bit field:
Bit
00
01
02
03
07
08
Dependency:
Refer to: p1645
434
Signal name
Power up excitation
Excitation no OFF2
Excitation no OFF3
Excitation operation enable
Excitation acknowledge fault
Reserved
Reserved
Signal name
Excitation ready for switching on feedback
signal
Excitation ready feedback signal
Excitation operational feedback signal
Excitation group signal fault
Excitation group signal alarm
Excitation at the voltage limit
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
5.0 [s]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
-
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: 6495
Unit selection: -
Expert list: 1
Factory setting
0.8 [s]
Access level: 2
Func. diagram: 6495
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
-
-
Access level: 2
Func. diagram: 6495
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
SINAMICS G130/G150
FP
-
-
-
-
-
-
-
FP
-
-
-
-
-
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents