2 Parameters
2.2 List of parameters
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Prerequisite: The DI/DO must be set as an output (p0728.11 = 1).
DI/DO: Bidirectional Digital Input/Output
p0742
BI: CU signal source for terminal DI/DO 12 / CU S_src DI/DO 12
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Unsigned32 / Binary
CU_G130_DP,
P-Group: Commands
CU_G150_DP
Not for motor type: -
Min
-
Description:
Sets the signal source for terminal DI/DO 12 (X132.9 / X131.1).
Regarding the terminal designation:
The first designation is valid for CU320, the second for CU310.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Prerequisite: The DI/DO must be set as an output (p0728.12 = 1).
DI/DO: Bidirectional Digital Input/Output
p0743
BI: CU signal source for terminal DI/DO 13 / CU S_src DI/DO 13
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Unsigned32 / Binary
CU_G130_DP,
P-Group: Commands
CU_G150_DP
Not for motor type: -
Min
-
Description:
Sets the signal source for terminal DI/DO 13 (X132.10 / X131.2).
Regarding the terminal designation:
The first designation is valid for CU320, the second for CU310.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Prerequisite: The DI/DO must be set as an output (p0728.13 = 1).
DI/DO: Bidirectional Digital Input/Output
p0744
BI: CU signal source for terminal DI/DO 14 / CU S_src DI/DO 14
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Unsigned32 / Binary
CU_G130_DP,
P-Group: Commands
CU_G150_DP
Not for motor type: -
Min
-
Description:
Sets the signal source for terminal DI/DO 14 (X132.12 / X131.4).
Regarding the terminal designation:
The first designation is valid for CU320, the second for CU310.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Prerequisite: The DI/DO must be set as an output (p0728.14 = 1).
DI/DO: Bidirectional Digital Input/Output
258
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 1
Func. diagram: 2119, 2132
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: 2132
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: 2133
Unit selection: -
Expert list: 1
Factory setting
0