2 Parameters
2.2 List of parameters
p2021
Field bus interface address / Field bus address
CU_G130_DP,
Can be changed: T
CU_G150_DP
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
0
Description:
Displays or sets the address for the fieldbus interface USS.
The address can be set as follows:
1) Using the address switch on the Control Unit.
--> p2021 displays the address setting.
--> A change only becomes effective after a POWER ON.
2) Using p2021
--> Only if an address of 0 or an address that is invalid for the fieldbus selected in p2030 has been set using the
address switch.
--> The address is saved in a non-volatile fashion using the function "copy from RAM to ROM".
--> A change only becomes effective after a POWER ON.
Dependency:
Refer to: p2030
Note:
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
The parameter is set to the factory setting when the protocol is reselected.
p2022
Field bus int USS PZD no. / Field bus USS PZD
CU_G130_DP,
Can be changed: T
CU_G150_DP
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
0
Description:
Sets the number of 16-bit words in the PZD part of the USS telegram for the field bus interface.
Dependency:
Refer to: p2030
Note:
The parameter is not influenced by setting the factory setting.
p2023
Field bus int USS PKW no. / Field bus USS PKW
CU_G130_DP,
Can be changed: T
CU_G150_DP
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
0
Description:
Sets the number of 16-bit words in the PKW part of the USS telegram for the field bus interface.
Value:
0:
3:
4:
127:
Dependency:
Refer to: p2030
Note:
The parameter is not influenced by setting the factory setting.
496
PKW 0 words
PKW 3 words
PKW 4 words
PKW variable
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
31
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
16
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
127
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: 9310
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 9310
Unit selection: -
Expert list: 1
Factory setting
2
Access level: 2
Func. diagram: 9310
Unit selection: -
Expert list: 1
Factory setting
127
SINAMICS G130/G150