r4055[0...1]
CO: TB30 analog inputs actual value in percent / TB30 AI value in %
TB30
Can be changed: -
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
- [%]
Description:
Displays the currently referred input value of the analog inputs of Terminal Board 30 (TB30).
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note:
AI: Analog Input
p4056[0...1]
TM31 analog inputs type / TM31 AI type
TM31
Can be changed: U, T
Data type: Integer16
P-Group: Terminals
Not for motor type: -
Min
0
Description:
Sets the type of analog inputs of Terminal Module 31 (TM31).
p4056[x] = 0, 4 correspond to a voltage input (r4052, p4057, p4059 are displayed in V).
p4056[x] = 2, 3, 5 correspond to a current input (r4052, p4057, p4059 are displayed in mA).
In addition, the associated switch S5 must be appropriately set.
AI 0: S5.0 = V --> voltage input, S5.0 = I --> current input (burden resistor = 250 Ohm)
AI 1: S5.1 = V --> voltage input, S5.1 = I --> current input (burden resistor = 250 Ohm)
Value:
0:
2:
3:
4:
5:
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Warning:
The maximum voltage difference between the analog input terminals AI+, AI- and the ground of the TM31 (X520.6,
X530.3) may not exceed 35 V.
For operation with the load resistor switched in, the voltage between the differential inputs AI+ and AI- may not
exceed 15 V or the impressed current of 60 mA; if this is not carefully observed, the input will be damaged.
Notice:
For operation as a voltage input/current input, switch S5.0 or S5.1 must be appropriately set.
Note:
When changing p4056, the parameters of the scaling characteristic (p4057, p4058, p4059, p4060) are overwritten
with the following default values:
For p4056 = 0, 4, p4057 is set to 0.0 V, p4058 to 0.0 %, p4059 to 10.0 V and p4060 to 100.0 %.
For p4056 = 2, 5, p4057 is set to 0.0 mA, p4058 to 0.0 %, p4059 to 20.0 mA and p4060 to 100.0 %.
For p4056 = 3, p4057 is set to 4.0 mA, p4058 to 0.0 %, p4059 to 20.0 mA and p4060 to 100.0 %.
r4056[0...1]
TB30 analog inputs type / TB30 AI type
TB30
Can be changed: -
Data type: Integer16
P-Group: Terminals
Not for motor type: -
Min
4
Description:
Displays the type of analog inputs.
Value:
4:
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Unipolar voltage input (0 V ... +10 V)
Unipolar current input (0 mA ... +20 mA)
Unipolar current input monitored (+4 mA to +20 mA)
Bipolar voltage input (-10 V ... +10 V)
Bipolar current input (-20 mA to +20 mA)
Bipolar voltage input (-10 V ... +10 V)
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
- [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
5
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
4
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: 9099, 9104
Unit selection: -
Expert list: 1
Factory setting
- [%]
Access level: 1
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
4
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
649