2 Parameters
2.2 List of parameters
Note:
A change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
CBE20: Communication Board Ethernet 20
p8836
SINAMICS link node address / Node address
CU_G130_PN (PN
Can be changed: C1(1)
CBE20),
Data type: Unsigned16
CU_G150_PN (PN
P-Group: Communications
CBE20),
Not for motor type: -
CU_G130_DP (PN
CBE20),
Min
CU_G150_DP (PN
0
CBE20)
Description:
Selects the node address for the SINAMICS Link on the Communication Board Ethernet 20 (CBE20).
p8836 = 0: SINAMICS Link deactivated
p8836 = 1 ... 64: SINAMICS Link node address
Dependency:
Refer to: p8811, p8835
Note:
The maximum number of permitted participant addresses is limited by the project selection p8811.
SINAMICS Link requires that the appropriate CBE20 firmware version is selected (p8835 = 3).
A change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
p8837
IF2 STW1.10 = 0 mode / IF2 STW1.10=0
VECTOR_G, B_INF,
Can be changed: T
ENC
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
0
Description:
Sets the processing mode for PROFIdrive STW1.10 "master control by PLC".
Generally, control world 1 is received with the first receive word (PZD1) (this is in conformance to the PROFIdrive
profile). The behavior of STW1.10 = 0 corresponds to that of the PROFIdrive profile. For other applications that
deviate from this, the behavior can be adapted using this particular parameter.
Value:
0:
1:
2:
Recommendation:
Do not change the setting p2037 = 0.
Note:
If the STW1 is not transferred according to the PROFIdrive with PZD1 (with bit 10 "master control by PLC"), then
p2037 should be set to 2.
p8839[0...1]
PZD interface hardware assignment / PZD IF HW assign
CU_G130_PN,
Can be changed: C1(1)
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: Communications
CU_G150_DP
Not for motor type: -
Min
0
Description:
Assignment of the hardware for cyclic communications via PZD interface 1 (IF1) and interface 2 (IF2).
Value:
0:
1:
2:
99:
Index:
[0] = Interface 1
[1] = Interface 2
Dependency:
Refer to: p2030, p8815
840
Freeze setpoints and continue to process sign-of-life
Freeze setpoints and sign-of-life
Do not freeze setpoints
Inactive
Control Unit onboard
COMM BOARD
Automatic
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
64
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
99
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 2198
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
2
Access level: 3
Func. diagram: 2197, 2198
Unit selection: -
Expert list: 1
Factory setting
99
SINAMICS G130/G150