2.2 List of parameters
p0925
PROFIdrive clock synchronous sign-of-life tolerance / PD SoL_tol
VECTOR_G (n/M),
Can be changed: U, T
ENC
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
0
Description:
Sets the number of tolerated consecutive sign-of-life errors of the clock-cycle synchronous master.
The sign-of-life signal is normally received in PZD4 (control word 2) from the master.
Dependency:
Refer to: p2045, r2065
Refer to: F01912
Note:
The sign-of-life monitoring is disabled for p0925 = 65535.
r0930
PROFIdrive operating mode / PD operating mode
VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Displays the operating mode.
1: Closed-loop speed controlled operation with ramp-function generator
2: Position controlled operation
3: Closed-loop speed controlled operation without ramp-function generator
r0944
CO: Counter for fault buffer changes / Fault buff change
All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
Display and connector output for the counter for changes of the fault buffer.
This counter is incremented every time the fault buffer changes.
Recommendation:
Used to check whether the fault buffer has been read out consistently.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2109
r0945[0...63]
Fault code / Fault code
All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays the numbers of faults that have occurred.
Dependency:
Refer to: r0947, r0948, r0949, r2109, r2130, r2133, r2136, r3120, r3122
Notice:
The properties of the fault buffer should be taken from the corresponding product documentation.
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Fault buffer structure (general principle):
r0945[0], r0949[0], r0948[0], r2109[0], r3115[0] --> actual fault case, fault 1
. . .
r0945[7], r0949[7], r0948[7], r2109[7], r3115[7] --> actual fault case, fault 8
292
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 2410
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: 8060
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: 8050, 8060
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS G130/G150