p3863
BI: Activating Braking Module DC link fast discharge / BM DC-dischg act
B_INF (Brk Mod ext)
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source to activate the DC link fast discharge.
The DC link fast discharge is started later with delay time (p3862) when the following conditions apply:
- BI: p3863 = 1 signal.
- an external line contactor is opened via r0863.1 "energize contactor".
The DC link fast discharge is interrupted when the following conditions apply:
- BI: p3863 = 0 signal.
- ON command for the infeed.
Recommendation:
The DC link fast discharge should be activated if there is an external line contactor and is correctly interconnected
(r0863.1, p0860). If the DC link fast discharge is not activated together with an external line contactor, then faults can
occur when precharging (e.g. F30027).
Dependency:
Refer to: r3864
Refer to: F30027
Note:
The DC link fast discharge is only possible for "booksize" formats. This function is not supported for "chassis"
formats.
r3864.0...7
BO: Braking Module DC link fast discharge / BM DC link dischg
B_INF (Brk Mod ext)
Can be changed: -
Data type: Unsigned32
P-Group: Commands
Not for motor type: -
Min
-
Description:
Signal to control (energize) terminal X21.2 "DC link fast discharge" on the Braking Module.
This binector output is used as signal source to interconnect to a digital output. The digital output must be connected
to terminal X21.2 of the particular Braking Module.
Bit field:
Bit
00
01
02
03
04
05
06
07
Dependency:
Refer to: p3863
Refer to: F30027
Warning:
It must be carefully ensured that the binector outputs BO: p3864.n are correctly interconnected and also that the
appropriate digital outputs are correctly connected up.
If the interconnection/connection is incorrect, in the case of an active DC link fast discharge, the software could
execute another function (incorrect function) via binector outputs BO: p3864.n or could also permanently control the
DC link fast discharge even if the line contactor is closed.
Note:
The DC link fast discharge is only possible for "booksize" formats. This function is not supported for "chassis"
formats.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
Fast discharge Braking Module 1
Fast discharge Braking Module 2
Fast discharge Braking Module 3
Fast discharge Braking Module 4
Fast discharge Braking Module 5
Fast discharge Braking Module 6
Fast discharge Braking Module 7
Fast discharge Braking Module 8
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
High
High
High
High
High
High
High
High
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 9951
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 9951
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
Low
Low
Low
Low
Low
Low
Low
Low