2 Parameters
2.2 List of parameters
520:
521:
522:
523:
524:
525:
526:
527:
769:
770:
771:
772:
773:
774:
775:
776:
777:
778:
779:
780:
781:
782:
783:
Index:
[0] = AND logic operation input 1
[1] = AND logic operation input 2
[2] = AND logic operation input 3
[3] = AND logic operation input 4
[4] = AND logic operation input 5
[5] = AND logic operation input 6
Note:
F-DO: Failsafe Digital Output
p10044[0...5]
SI TM54F F-DO 2 signal sources / SI F-DO 2 S_src
TM54F_MA,
Can be changed: C2(95)
TM54F_SL
Data type: Integer16
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Sets the signal sources for F-DO 2.
The 6 signal sources in p10044[0...5] are AND'ed and the result is output at F-DO 2.
Value:
0:
1:
2:
3:
4:
5:
6:
7:
8:
9:
10:
11:
12:
13:
14:
15:
257:
258:
259:
260:
261:
262:
263:
1052
Drive group 3 SOS selected
Drive group 3 internal event
Drive group 3 active SLS stage bit 0
Drive group 3 active SLS stage bit 1
Drive group 3 SDI positive active
Drive group 3 SDI negative active
Drive group 3 SLP active
Drive group 3 active SLP area
Drive group 4 STO active
Drive group 4 SS1 active
Drive group 4 SS2 active
Drive group 4 SOS active
Drive group 4 SLS active
Drive group 4 SSM feedback signal active
Drive group 4 safe state
Drive group 4 SOS selected
Drive group 4 internal event
Drive group 4 active SLS stage bit 0
Drive group 4 active SLS stage bit 1
Drive group 4 SDI positive active
Drive group 4 SDI negative active
Drive group 4 SLP active
Drive group 4 active SLP area
No function
Drive group 1 STO active
Drive group 1 SS1 active
Drive group 1 SS2 active
Drive group 1 SOS active
Drive group 1 SLS active
Drive group 1 SSM feedback signal active
Drive group 1 safe state
Drive group 1 SOS selected
Drive group 1 internal event
Drive group 1 active SLS stage bit 0
Drive group 1 active SLS stage bit 1
Drive group 1 SDI positive active
Drive group 1 SDI negative active
Drive group 1 SLP active
Drive group 1 active SLP area
Drive group 2 STO active
Drive group 2 SS1 active
Drive group 2 SS2 active
Drive group 2 SOS active
Drive group 2 SLS active
Drive group 2 SSM feedback signal active
Drive group 2 safe state
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
783
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 2902, 2907
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents