Siemens G130 List Manual page 722

Hide thumbs Also See for G130:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p4800
Function generator control / FG control
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: Trace and function generator
CU_G150_DP
Not for motor type: -
Min
0
Description:
The function generator is started with p4800 = 1.
The signal is only generated for a 1 signal of binector input p4819.
Value:
0:
1:
2:
3:
Dependency:
Refer to: p4819
r4805
Function generator status / FG status
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: Trace and function generator
CU_G150_DP
Not for motor type: -
Min
0
Description:
Displays the actual status of the function generator.
Value:
0:
1:
2:
3:
4:
5:
6:
Dependency:
Refer to: p4800, p4819
r4806.0
BO: Function generator status signal / FG status signal
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: Unsigned32
CU_G130_DP,
P-Group: Trace and function generator
CU_G150_DP
Not for motor type: -
Min
-
Description:
Displays the status of the function generator.
0 signal: Function generator inactive
1 signal: Function generator running
Bit field:
Bit
00
722
Stop function generator
Start function generator
Check function generator parameterization
Start function generator without enable signals
Inactive
Generate accelerating ramp to offset
Generate parameterized signal shape
Generate braking ramp
Function generator stopped due to missing enable signals
Function generator waits for BI: p4819
Function generator parameterization has been checked
Signal name
Bit 0
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
6
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
ON
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
-
0 signal
OFF
SINAMICS G130/G150
FP
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150