Dependency:
Refer to: p8925, r8934
Notice:
When the DHCP mode is active (p8924 not equal to 0), then PROFINET communication via this interface is no longer
possible! However, the interface can be used by the STARTER/SCOUT commissioning tool.
Note:
The interface configuration (p8920 and following) is activated with p8925.
The active DHCP mode is displayed in parameter r8934.
The parameter is not influenced by setting the factory setting.
p8925
PN interface configuration / PN IF config
CU_G130_PN,
Can be changed: U, T
CU_G150_PN
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Setting to activate the interface configuration for the onboard PROFINET interface on the Control Unit.
p8925 is automatically set to 0 at the end of the operation.
Value:
0:
1:
2:
3:
Dependency:
Refer to: p8920, p8921, p8922, p8923, p8924
Refer to: A08563
Notice:
When the DHCP mode is active (p8924 > 0), then PROFINET communication via this interface is no longer possible!
However, the interface can be used by the STARTER/SCOUT commissioning tool.
Note:
When a project is downloaded, the interface configuration is only activated if, in the offline project, parameter p8925
is set = 1 or 2.
For p8925 = 1:
The interface configuration (p8920 and following) is activated.
For p8925 = 2:
The interface configuration (p8920 and following) is activated and saved to non-volatile memory.
For p8925 = 3:
Restores all memory locations for the interface configuration to the factory settings.
The factory settings for the interface configuration are loaded on activation (p8925 = 1) or at the next POWER ON.
p8929
PN remote controller number / PN rem ctrl num
CU_G130_PN,
Can be changed: C1(1)
CU_G150_PN
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
1
Description:
Sets the number of remote controllers expected for PROFINET onboard.
The "Shared Device" functionality is activated with p8929 = 2.
The drive is being accessed by two PROFINET controllers simultaneously:
- automation controller (SIMOTION or SIMATIC A-CPU).
- safety controller (SIMATIC F-CPU).
Value:
1:
2:
Notice:
The F CPU may only use PROFIsafe telegrams.
Note:
A change only becomes effective after POWER ON, reset or download.
For PROFINET system redundancy, p8929 should be set = 1.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
No function
Activate configuration
Activate and save configuration
Delete configuration
Automation or Safety
Automation and Safety
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
881