2 Parameters
2.2 List of parameters
p1726[0...n]
Quadrature arm decoupling scaling / Transv_decpl scal
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
0.0 [%]
Description:
Sets the scaling of the quadrature arm decoupling
Note:
This parameter is ineffective for sensorless vector control. In this case, p1727 is always used. If p1726 is set to 0,
then the quadrature de-coupling is deactivated. The integral component of the Isd current controller remains effective
in the complete speed control range.
For the closed-loop control of synchronous motors, this parameter is used to scale the current controller de-coupling.
p1727[0...n]
Quadrature arm decoupling at voltage limit scaling / TrnsvDecplVmaxScal
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
0.0 [%]
Description:
Sets the scaling of quadrature arm decoupling when the voltage limit is reached.
r1728
De-coupling voltage in-line axis / U_dir-axis_decoupl
VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
- [Vrms]
Description:
Displays the actual output of the quadrature channel de-coupling for the d axis.
r1729
De-coupling voltage quadrature axis / U_quad_decoupl
VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
- [Vrms]
Description:
Displays the actual output of the quadrature channel de-coupling for the q axis.
p1730[0...n]
Isd controller integral component shutdown threshold / Isd ctrl Tn shutd
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: PMSM, SESM, REL
Min
30 [%]
Description:
Sets the speed threshold for deactivating the integral component of the Isd controller.
The d current controller is only effective as P controller for speeds greater than the threshold value. Instead of the
integral component, the quadrature arm decoupling is effective.
444
Calculated: CALC_MOD_ALL
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
200.0 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
200.0 [%]
Calculated: -
Dyn. index: -
Unit group: 5_1
Scaling: p2001
Max
- [Vrms]
Calculated: -
Dyn. index: -
Unit group: 5_1
Scaling: p2001
Max
- [Vrms]
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
150 [%]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 4
Func. diagram: 6714
Unit selection: -
Expert list: 1
Factory setting
75.0 [%]
Access level: 4
Func. diagram: 6714
Unit selection: -
Expert list: 1
Factory setting
50.0 [%]
Access level: 3
Func. diagram: 6714
Unit selection: p0505
Expert list: 1
Factory setting
- [Vrms]
Access level: 3
Func. diagram: 6714
Unit selection: p0505
Expert list: 1
Factory setting
- [Vrms]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
30 [%]