p4679[0...n]
Analog sensor LVDT phase / An_sens LVDT ph
VECTOR_G, ENC
Can be changed: C2(4), T
Data type: FloatingPoint32
P-Group: Encoder
Not for motor type: -
Min
-360.00 [°]
Description:
Sets the phase for the LVDT sensor.
p4680[0...n]
Zero mark monitoring tolerance permissible / ZM_monit tol perm
VECTOR_G, ENC
Can be changed: C2(4)
Data type: Unsigned32
P-Group: Encoder
Not for motor type: -
Min
0
Description:
Sets the permissible tolerance in encoder pulses for the zero mark distance in the context of zero mark monitoring.
Causes fault F3x100 to appear less frequently.
Dependency:
Refer to: F31100
p4681[0...n]
Zero mark monitoring tolerance window limit 1 positive / ZM tol lim 1 pos
VECTOR_G, ENC
Can be changed: C2(4)
Data type: Unsigned32
P-Group: Encoder
Not for motor type: -
Min
0
Description:
Sets the positive tolerance window in encoder pulses for limit 1 for the zero mark monitoring.
If the deviation is less than this limit, then the pulse number is not corrected. If it is higher than this limit, fault F3x131
is triggered.
If fault F3x131 is re-parameterized to alarm (A) or no message (N), the encoder pulses which have not been
corrected are added to the accumulator (p4688). The accumulator can be deactivated using p0437.7.
Dependency:
Refer to: p0437, p4688
Refer to: F31131
Note:
This monitoring is activated by setting p0437.2 = 1 (position actual value correction).
The positive limit describes additional pulses due to EMC.
p4682[0...n]
Zero mark monitoring tolerance window limit 1 negative / ZM tol lim 1 neg
VECTOR_G, ENC
Can be changed: C2(4)
Data type: Integer32
P-Group: Encoder
Not for motor type: -
Min
-1001
Description:
Sets the negative tolerance window in encoder pulses for limit 1 for the zero mark monitoring.
If the deviation is less than this limit, the PPR is not corrected. If it is higher than this limit, fault F3x131 is triggered.
If fault F3x131 is re-parameterized to alarm (A) or no message (N), the encoder pulses which have not been
corrected are added to the accumulator (p4688). The accumulator can be deactivated using p0437.7.
Dependency:
Refer to: p0437, p4681, p4688
Refer to: F31131
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
360.00 [°]
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
1000
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
1000
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
0
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00 [°]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
4
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
2
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-1001
695