Dependency:
Refer to: p2140, r2197
Refer to: A07821
Caution:
The filter monitoring function is deactivated with 2155 = 0.0.
Note:
The parameter is used as alarm threshold for underspeed monitoring.
Underspeed monitoring for a separately excited synchronous motor in closed-loop torque control without an encoder
(p0300 = 5, p1300 = 20, p1501 = 1 signal), is automatically activated internally, and can be manually activated with
p2149.6 = 1.
For separately excited synchronous motors, when exiting commissioning (p0340 = 5), this parameter is automatically
assigned 1.5 * p1755.
p2156[0...n]
On delay comparison value reached / t_on cmpr val rchd
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.0 [ms]
Description:
Sets the switch-in delay time for the signal "comparison value reached" (BO: r2199.1).
Dependency:
Refer to: p2141, p2142, r2199
p2161[0...n]
Speed threshold 3 / n_thresh val 3
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.00 [rpm]
Description:
Sets the speed threshold value for the signal "|n_act| < speed threshold value 3" (BO: r2199.0).
Dependency:
Refer to: p2142, r2199
Refer to: F07822
Caution:
The threshold monitoring function is deactivated with 2161 = 0.0.
Note:
The parameter is used as fault threshold for underspeed monitoring
Underspeed monitoring for a separately excited synchronous motor in closed-loop torque control without an encoder
(p0300 = 5, p1300 = 20, p1501 = 1 signal), is automatically activated internally, and can be manually activated with
p2149.6 = 1.
For separately excited synchronous motors, when exiting commissioning (p0340 = 5), this parameter is automatically
assigned p1755.
p2162[0...n]
Hysteresis speed n_act > n_max / Hyst n_act>n_max
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: -
Min
0.00 [rpm]
Description:
Sets the hysteresis speed (bandwidth) for the signal "n_act > n_max" (BO: r2197.6).
Dependency:
Refer to: r1084, r1087, r2197
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10000.0 [ms]
Calculated:
CALC_MOD_LIM_REF
Dyn. index: DDS, p0180
Unit group: 3_1
Scaling: -
Max
210000.00 [rpm]
Calculated:
CALC_MOD_LIM_REF
Dyn. index: DDS, p0180
Unit group: 3_1
Scaling: -
Max
60000.00 [rpm]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 8010
Unit selection: -
Expert list: 1
Factory setting
0.0 [ms]
Access level: 3
Func. diagram: 8010, 8011
Unit selection: p0505
Expert list: 1
Factory setting
5.00 [rpm]
Access level: 2
Func. diagram: 8010
Unit selection: p0505
Expert list: 1
Factory setting
0.00 [rpm]
553