Siemens G130 List Manual page 279

Hide thumbs Also See for G130:
Table of Contents

Advertisement

p0852[0...n]
BI: Enable operation/inhibit operation / Enable operation
VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for the command "enable operation/inhibit operation".
For the PROFIdrive profile, this command corresponds to control word 1 bit 3 (STW1.3).
BI: p0852 = 0 signal
Inhibit operation (suppress pulses).
BI: p0852 = 1 signal
Enable operation (pulses can be enabled).
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0854[0...n]
BI: Control by PLC/no control by PLC / Master ctrl by PLC
VECTOR_G, B_INF
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for the command "control by PLC/no control by PLC".
For the PROFIdrive profile, this command corresponds to control word 1 bit 10 (STW1.10).
BI: p0854 = 0 signal
No control by PLC
BI: p0854 = 1 signal
Master control by PLC.
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
This bit is used to initiate a response for the drives when the control fails (F07220). If there is no control available,
then binector input p0854 should be set to 1.
If a control is available, then STW1.10 must be set to 1 (PZD1) so that the received data is updated. This applies
regardless of the setting in p0854 and even in the case of free telegram configuration (p0922 = 999).
p0854
BI: Control by PLC/no control by PLC / Master ctrl by PLC
ENC
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for the command "control by PLC/no control by PLC".
For the PROFIdrive profile, this command corresponds to control word 1 bit 10 (STW1.10).
BI: p0854 = 0 signal
No control by PLC
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 2501, 8820,
8920
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 2501, 8720,
8820, 8920
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 2501, 8720,
8820, 8920
Unit selection: -
Expert list: 1
Factory setting
1
279