Siemens G130 List Manual page 704

Hide thumbs Also See for G130:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
[2] = Trace 0 PINx with DO Id and chart Id
[3] = Trace 0 PINx with block Id and PIN Id
[4] = Trace 1 PINy with DO Id and chart Id
[5] = Trace 1 PINy with block Id and PIN Id
Dependency:
Only effective when p4710 does not equal 1.
Note:
It only makes sense to trace the PINs using the commissioning software.
For index 2(4) and 3(5) equal to zero, index 0(1) can only be written and vice versa.
For index 0 ... 1:
Here, the trigger signal for trace 0 or 1 is entered as parameter in the BICO format.
For trace with a physical address (p4789), the data type of the trigger signal is set here.
For index 2 ...3:
The triggering PIN for trace 0 is entered here.
Index 2 bit 31 ... 16: Number of the Drive Object (DO), bit 15 ... 0: Number of the chart
Index 3 bit 31 ... 16: Number of the block, bit 15 ... 0: Number of the PIN
For index 4 ... 5:
The triggering PIN for trace 1 is entered here.
Index 4 bit 31 ... 16: Number of the Drive Object (DO), bit 15 ... 0: Number of the chart
Index 5 bit 31 ... 16: Number of the block, bit 15 ... 0: Number of the PIN
p4712[0...1]
Trace trigger threshold / Trace trig_thresh
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Trace and function generator
CU_G150_DP
Not for motor type: -
Min
-340.28235E36
Description:
Sets the trigger threshold for the trace.
Index:
[0] = Trace 0
[1] = Trace 1
Dependency:
Only effective when p4710 = 2, 3.
p4713[0...1]
Trace tolerance band trigger threshold 1 / Trace trig thr 1
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Trace and function generator
CU_G150_DP
Not for motor type: -
Min
-340.28235E36
Description:
Sets the first trigger threshold for trigger via tolerance band.
Index:
[0] = Trace 0
[1] = Trace 1
Dependency:
Only effective when p4710 = 4, 5.
p4714[0...1]
Trace tolerance band trigger threshold 2 / Trace trig thr 2
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Trace and function generator
CU_G150_DP
Not for motor type: -
Min
-340.28235E36
Description:
Sets the second trigger threshold for trigger via tolerance band
Index:
[0] = Trace 0
[1] = Trace 1
Dependency:
Only effective when p4710 = 4, 5.
704
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
340.28235E36
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
340.28235E36
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
340.28235E36
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
0.00
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
0.00
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
0.00
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents