2 Parameters
2.2 List of parameters
r10055
SI TM54F communication status drive-specific / SI comm_stat drv
TM54F_MA,
Can be changed: -
TM54F_SL
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Displays the communication status of the individual drives with the Terminal Module 54F (TM54F).
For r10055 = 0, the following applies:
All drives assigned in p10010 communicate with the TM54F.
Bit field:
Bit
00
01
02
03
04
05
r10056.0
CO/BO: SI TM54F status / SI stat
TM54F_MA
Can be changed: -
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Display and BICO output for the status of the Terminal Module 54F (TM54F).
Bit field:
Bit
00
p10061
SI TM54F password input / SI password inp
TM54F_MA,
Can be changed: U, T
TM54F_SL
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
0000 hex
Description:
Enters the Safety Integrated password for the Terminal Module 54F (TM54F).
This password is required to change the safety-relevant parameters.
1058
Signal name
Communication between drive 1 and
TM54F
Communication between drive 2 and
TM54F
Communication between drive 3 and
TM54F
Communication between drive 4 and
TM54F
Communication between drive 5 and
TM54F
Communication between drive 6 and
TM54F
Signal name
Test stop status
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Not configured
Not configured
Not configured
Not configured
Not configured
Not configured
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Active
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
FFFF FFFF hex
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
Configured
Configured
Configured
Configured
Configured
Configured
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
Inactive
Access level: 3
Func. diagram: 2891
Unit selection: -
Expert list: 1
Factory setting
0000 hex