Siemens G130 List Manual page 725

Hide thumbs Also See for G130:
Table of Contents

Advertisement

p4820
Function generator signal shape / FG signal shape
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: Trace and function generator
CU_G150_DP
Not for motor type: -
Min
1
Description:
Sets the signal to be generated for the function generator.
Value:
1:
2:
3:
4:
5:
p4821
Function generator period / FG period duration
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Trace and function generator
CU_G150_DP
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the period of the signal to be generated for the function generator.
Dependency:
Ineffective when p4820 = 4 (PRBS).
p4822
Function generator pulse width / FG pulse width
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Trace and function generator
CU_G150_DP
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the pulse width for the signal to be generated for the function generator.
Dependency:
Only effective when p4820 = 1 (square-wave).
p4823
Function generator bandwidth / FG bandwidth
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Trace and function generator
CU_G150_DP
Not for motor type: -
Min
0.0025 [Hz]
Description:
Sets the bandwidth for the signal to be generated for the function generator.
Dependency:
Only effective when p4820 = 4 (PRBS).
Refer to: p4830
Refer to: A02041
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Square-wave
Staircase
Delta
Binary noise - PRBS (Pseudo Random Binary Signal)
Sine-wave
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
5
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
60000.00 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
60000.00 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
16000.0000 [Hz]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
1
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
1000.00 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
500.00 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
4000.0000 [Hz]
725

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents