2 Parameters
2.2 List of parameters
p1110[0...n]
BI: Inhibit negative direction / Inhib neg dir
VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source to disable the negative direction.
Dependency:
Refer to: p1111
p1111[0...n]
BI: Inhibit positive direction / Inhib pos dir
VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source to disable the positive direction.
Dependency:
Refer to: p1110
r1112
CO: Speed setpoint after minimum limiting / n_set aft min_lim
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
- [rpm]
Description:
Displays the speed setpoint after the minimum limiting.
Dependency:
Refer to: p1091, p1092, p1093, p1094, p1101
p1113[0...n]
BI: Setpoint inversion / Setp inv
VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source to invert the setpoint.
Dependency:
Refer to: r1198
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
r1114
CO: Setpoint after the direction limiting / Setp after limit
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
- [rpm]
Description:
Displays the speed/velocity setpoint after the changeover and limiting the direction.
324
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: 3_1
Scaling: p2000
Max
- [rpm]
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: 3_1
Scaling: p2000
Max
- [rpm]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 2505, 3040
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2505, 3040
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 3050
Unit selection: p0505
Expert list: 1
Factory setting
- [rpm]
Access level: 3
Func. diagram: 2441, 2442,
2505, 3040
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 3001, 3040,
3050
Unit selection: p0505
Expert list: 1
Factory setting
- [rpm]
SINAMICS G130/G150