2 Parameters
2.2 List of parameters
p4824
Function generator amplitude / FG amplitude
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Trace and function generator
CU_G150_DP
Not for motor type: -
Min
-1600.00 [%]
Description:
Sets the amplitude for the signal to be generated for the function generator.
Dependency:
Units are dependent on p4810.
If p4810 = 1, 2, 4: The amplitude is referred to p2002 (reference current).
If p4810 = 3, 5: The amplitude is referred to p2000 (reference speed).
p4825
Function generator 2nd amplitude / FG 2nd amplitude
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Trace and function generator
CU_G150_DP
Not for motor type: -
Min
-1600.00 [%]
Description:
Sets the second amplitude for the signal to be generated for the function generator.
Dependency:
Only effective for p4820 = 2 (staircase).
Units are dependent on p4810.
If p4810 = 1, 2, 4: The amplitude is referred to p2002 (reference current).
If p4810 = 3, 5: The amplitude is referred to p2000 (reference speed).
p4826
Function generator offset / FG offset
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Trace and function generator
CU_G150_DP
Not for motor type: -
Min
-1600.00 [%]
Description:
Sets the offset (DC component) of the signal to be generated for the function generator.
Dependency:
Units are dependent on p4810.
If p4810 = 1, 2, 4: The offset is referred to p2002 (reference current).
If p4810 = 3, 5: The offset is referred to p2000 (reference speed).
If p4810 = 2: In order to avoid the undesirable effects of play (backlash), the offset does not act on the current
setpoint, but instead on the speed setpoint.
p4827
Function generator ramp-up time to offset / FG ramp-up offset
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Trace and function generator
CU_G150_DP
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the ramp-up time to the offset for the function generator.
726
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1600.00 [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1600.00 [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1600.00 [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
100000.00 [ms]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
5.00 [%]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
7.00 [%]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
0.00 [%]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
32.00 [ms]
SINAMICS G130/G150