2 Parameters
2.2 List of parameters
p4075[0...1]
TB30 analog outputs activate absolute value generation / TB30 AO absVal act
TB30
Can be changed: T
Data type: Integer16
P-Group: Terminals
Not for motor type: -
Min
0
Description:
Activates the absolute value generation for the analog outputs of the Terminal Board 30 (TB30).
Value:
0:
1:
Index:
[0] = AO 0 (X482.5/X482.6)
[1] = AO 1 (X482.7/X482.8)
p4076[0...1]
TM31 analog outputs type / TM31 AO type
TM31
Can be changed: U, T
Data type: Integer16
P-Group: Terminals
Not for motor type: -
Min
0
Description:
Sets the type of analog outputs of Terminal Module 31 (TM31).
p4076[x] = 1, 4 correspond to a voltage output (p4074, p4078, p4080, p4083 are displayed in V).
p4076[x] = 0, 2, 3 correspond to a current output (p4074, p4078, p4080, p4083 are displayed in mA).
Value:
0:
1:
2:
3:
4:
Index:
[0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency:
Refer to: p4077, p4078, p4079, p4080
Note:
When changing p4076, the parameters of the scaling characteristic (p4077, p4078, p4079, p4080) are overwritten
with the following default values:
For p4076 = 0, 3, p4077 is set to 0.0 %, p4078 to 0.0 mA, p4079 to 100.0 % and p4080 to 20.0 mA.
For p4076 = 1, 4, p4077 is set to 0.0 %, p4078 to 0.0 V, p4079 to 100.0 % and p4080 to 10.0 V.
For p4076 = 2, p4077 is set to 0.0 %, p4078 to 4.0 mA, p4079 to 100.0 % and p4080 to 20.0 mA.
r4076[0...1]
TB30 analog outputs type / TB30 AO type
TB30
Can be changed: -
Data type: Integer16
P-Group: Terminals
Not for motor type: -
Min
4
Description:
Displays the type of analog outputs of the Terminal Board 30 (TB30).
Value:
4:
Index:
[0] = AO 0 (X482.5/X482.6)
[1] = AO 1 (X482.7/X482.8)
658
No absolute value generation
Absolute value generation switched in
Current output (0 mA ... +20 mA)
Voltage output (0 V ... +10 V)
Current output (+4 mA ... +20 mA)
Current output (-20 mA ... +20 mA)
Voltage output (-10 V ... +10 V)
Voltage output (-10 V ... +10 V)
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
4
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
4
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 9106
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: 9572
Unit selection: -
Expert list: 1