p2292
CO: Technology controller minimum limiting / Tec_ctrl min_lim
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-200.00 [%]
Description:
Sets the minimum limit of the technology controller.
Dependency:
Refer to: p2291
Caution:
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2293
Technology controller ramp-up/ramp-down time / Tec_ctr t_RU/RD
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
0.00 [s]
Description:
Sets the ramping time for the output signal of the technology controller.
Dependency:
Refer to: p2291, p2292
Note:
The time refers to the set maximum and minimum limits (p2291, p2292).
r2294
CO: Technology controller output signal / Tec_ctrl outp_sig
VECTOR_G
Can be changed: -
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
- [%]
Description:
Display and connector output for the output signal of the technology controller.
Dependency:
Refer to: p2295
p2295
CO: Technology controller output scaling / Tec_ctrl outp scal
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-100.00 [%]
Description:
Sets the scaling for the output signal of the technology controller.
p2296[0...n]
CI: Technology controller output scaling / Tec_ctrl outp scal
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: Unsigned32 / FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-
Description:
Sets the signal source for the scaling value of the technology controller.
Dependency:
Refer to: p2295
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
100.00 [s]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
- [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
100.00 [%]
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: PERCENT
Max
-
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0.00 [%]
Access level: 3
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
1.00 [s]
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
- [%]
Access level: 3
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
2295[0]