For 1PQ8 motors, p0335 should be set to 5 as these motors are force-ventilated motors.
The setting p0335 = 128 applies for 1LA7 motors, frame size 56 (these are operated without a fan).
r0336[0...n]
Actual rated motor frequency / Mot f_rated act
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
- [Hz]
Description:
Displays the rated frequency of the motor.
For p0310 > 0, this value is displayed.
Dependency:
Refer to: p0311, p0314
Note:
For p0310 = 0 or for synchronous motors, the rated motor frequency r0336 is calculated from the rated speed and the
pole pair number.
For p0310 > 0, this value is displayed (not for synchronous motors).
r0337[0...n]
Rated motor EMF / Mot EMF_rated
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: REL, RESM
Min
- [Vrms]
Description:
Displays the rated EMF of the motor.
Note:
EMF: Electromotive force
r0339[0...n]
Rated motor voltage / Mot U_rated
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: REL
Min
- [Vrms]
Description:
Displays the rated motor voltage.
Note:
For induction motors (p0300 = 1xx) the parameter is set to p0304.
For synchronous motors, parameter r0339 = p0304 is displayed. If p0304 = 0, then r0339 is calculated from p0305
and p0316.
p0340[0...n]
Automatic calculation motor/control parameters / Calc auto par
VECTOR_G
Can be changed: C2(3), T
Data type: Integer16
P-Group: Motor
Not for motor type: -
Min
0
Description:
Setting to automatically calculate motor parameters and U/f open-loop and closed-loop control parameters from the
rating plate data.
Value:
0:
1:
2:
3:
4:
5:
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
No calculation
Complete calculation
Calculation of equivalent circuit diagram parameters
Calculation of closed-loop control parameters
Calculation of controller parameters
Calculation of technological limits and threshold values
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
- [Hz]
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
- [Vrms]
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
- [Vrms]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
5
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [Hz]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [Vrms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [Vrms]
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0