2 Parameters
2.2 List of parameters
p9521[0...7]
SI Motion gearbox enc (motor)/load denominator (Control Unit) / SI Mtn gear den CU
VECTOR_G
Can be changed: C2(95)
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
1
Description:
Sets the denominator for the gearbox between the encoder (or motor in the case of encoderless monitoring
functions) and the load. The active gearbox stage can be switched over via PROFIsafe.
Index:
[0] = Gearbox 1
[1] = Gearbox 2
[2] = Gearbox 3
[3] = Gearbox 4
[4] = Gearbox 5
[5] = Gearbox 6
[6] = Gearbox 7
[7] = Gearbox 8
Dependency:
Refer to: p9522
p9522[0...7]
SI Motion gearbox encoder (motor)/load numerator (Control Unit) /
SI Mtn gear num CU
VECTOR_G
Can be changed: C2(95)
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
1
Description:
Sets the numerator for the gearbox between the encoder (or motor in the case of encoderless monitoring functions)
and the load. The active gearbox stage can be switched over via PROFIsafe.
Index:
[0] = Gearbox 1
[1] = Gearbox 2
[2] = Gearbox 3
[3] = Gearbox 4
[4] = Gearbox 5
[5] = Gearbox 6
[6] = Gearbox 7
[7] = Gearbox 8
Dependency:
Refer to: p9521
Note:
In the case of encoderless monitoring functions, the pole pair number must be multiplied by the numerator of the
gearbox ratio.
Example:
Gearbox ratio 1:4, pole pair number (r0313) = 2
--> p9521 = 1, p9522 = 8 (4 x 2)
p9523
SI Motion redundant coarse pos. value valid bits (Control Unit) / Valid bits CU
VECTOR_G
Can be changed: C2(95)
Data type: Unsigned16
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Sets the number of valid bits of the redundant coarse position value.
The encoder that is used for the safe motion monitoring functions on the Control Unit must be parameterized in this
parameter.
Dependency:
Refer to: r0470, p9323
936
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2147000000
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2147000000
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
16
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
9