p1811[0...n]
Pulse frequency wobbulation amplitude / Puls wobb ampl
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
0 [%]
Description:
Sets the amplitude of the statistical wobbulation signal.
This signal is used to vary the pulse frequency to create a more pleasant sound.
Note:
p1811 > 0 is possible, if the following applies:
- configuration: p1810.2 = 1 (wobbulation activated)
- pulse frequency: p1800 <= 1000 / p115[0]
- output filter, filter type: p0230 < 3 (no sine-wave filter)
p1812
BI: Offset calibration output current measurement / Off_calibr I_outp
VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Modulation
Not for motor type: -
Min
-
Description:
Sets the signal source to activate/deactivate offset calibration for output current measurement.
Caution:
The absence of offset calibration can have a negative effect on control properties. Offset calibration must be
performed before switching on the power unit for the first time after POWER ON.
Note:
Offset calibration is only performed with pulses suppressed and can take up to one second.
p1814[0...n]
Vdc filter dead band for modulation switchover / Vdc filt dead band
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
0.0 [%]
Description:
Sets the filter dead bandwidth for the DC link voltage signal to switch over the modulation type for optimized pulse
patterns.
The parameter value refers to the rated line voltage of the power unit.
Recommendation:
For power units with controlled regenerative line feedback, a value of approximately 2 % is recommended.
For all other power units, a value of approximately 8 % (as a result of the increased DC link voltage ripple under
load).
p1815
Phase for PWM generation subgroup / Ph for PWM subgr
VECTOR_G
Can be changed: U, T
Data type: Unsigned16
P-Group: Modulation
Not for motor type: -
Min
-
Description:
Sets bit 0 for recording the power unit in the subgroup for the "offset clocking".
Bit field:
Bit
00
Dependency:
Refer to: p1818, p1819
464
Signal name
Recording in subgroup for offset clocking
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
20 [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
12.0 [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0 [%]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.0 [%]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0001 bin
0 signal
No
SINAMICS G130/G150
FP
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents