p4098[0...1]
TM31 analog inputs simulation mode setpoint / TM31 AI sim setp
TM31
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
-20.000
Description:
Sets the setpoint for the input value in simulation mode of the analog inputs of Terminal Module 31 (TM31).
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
The simulation of an analog input is selected using p4097.
If AI x is parameterized as voltage input (p4056), then the setpoint is a voltage in V.
If AI x is parameterized as current input (p4056), then the setpoint is a current in mA.
Refer to: r4056, p4056, p4097
Note:
This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
p4098[0...1]
TB30 analog inputs simulation mode setpoint / TB30 AI sim setp
TB30
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
-11.000 [V]
Description:
Sets the setpoint for the input voltage in the simulation mode of the analog inputs of Terminal Board 30 (TB30).
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Dependency:
The simulation of an analog input is selected using p4097.
Refer to: p4097
Note:
This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
p4099[0...2]
TM31 inputs/outputs sampling time / TM31 I/O t_sample
TM31
Can be changed: C1(3)
Data type: FloatingPoint32
P-Group: Commands
Not for motor type: -
Min
0.00 [µs]
Description:
Sets the sampling time for the inputs and outputs of Terminal Module 31 (TM31).
Index:
[0] = Digital inputs/outputs (DI/DO)
[1] = Analog inputs (AI)
[2] = Analog outputs (AO)
Dependency:
The parameter can only be modified for p0009 = 3, 29.
The following applies for the sampling time:
The sampling times at a DRIVE-CLiQ line must be integral multiples of one another.
The sampling times of this TM must be an integral multiple of a servo or vector drive that exists in the system.
The minimum permissible sampling time is 125 µs.
The sampling times entered in index 0 (digital inputs/outputs) and index 2 (analog outputs) must always be greater
than or equal to the sampling time in index 1 (analog inputs).
Refer to: p0009, r0110, r0111
Notice:
The sampling times entered in index 0 (digital inputs/outputs) and index 2 (analog outputs) must always be greater
than or equal to the sampling time in index 1 (analog inputs).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
20.000
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
11.000 [V]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
5000.00 [µs]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
0.000
Access level: 2
Func. diagram: 9104
Unit selection: -
Expert list: 1
Factory setting
0.000 [V]
Access level: 3
Func. diagram: 9549, 9550
Unit selection: -
Expert list: 1
Factory setting
4000.00 [µs]