2 Parameters
2.2 List of parameters
p6903[0...n]
Voltage actual values, offset mode / U_ActVal offs mode
VECTOR_G (n/M)
Can be changed: U, T
Data type: Integer16
P-Group: Closed-loop control
Not for motor type: -
Min
0
Description:
Sets the offset mode for voltage actual value sensing.
When the mode is enabled (p6903 = 0), for a pulse inhibit for stator and excitation and zero speed, the offset
calibration is automatically started.
Offset calibration is inhibited when the mode is inhibited (p6903 = 1). The values last determined in p6870 and p6871
are saved. However, they can also be overwritten by a fixed value.
Value:
0:
1:
Dependency:
Refer to: p6870, p6871
Note:
Offset mode can only be set for actual value sensing functions that are available in the hardware.
r6991[0...4]
Recorder settings display / Rec setting displ
VECTOR_G (Rec),
Can be changed: -
B_INF (Rec)
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-
Description:
Displays the values calculated for the recorder
Index:
[0] = Actual trace number
[1] = Actual recording time
[2] = Actual pretrigger time
[3] = Actual post trigger time
[4] = Actual number of signals
Dependency:
Refer to: p6999
r6992.0...15
CO/BO: Recorder status word / Rec ZSW
VECTOR_G (Rec),
Can be changed: -
B_INF (Rec)
Data type: Unsigned16
P-Group: Displays, signals
Not for motor type: -
Min
-
Description:
Display and BICO output for the status word of the recorder.
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
746
Offset calculation enabled
Offset calculation inhibited
Signal name
Internal activation
External activation
Internal trigger
External trigger 1.1
External trigger 1.2
External trigger 1.3
External trigger 1.4
External trigger 2.1
External trigger 2.2
External trigger 2.3
Hardware trigger
Calculated: -
Dyn. index: p0150
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 4
Func. diagram: 8144
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 4
Func. diagram: 8144, 8145
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
Not set
Not set
Not set
Not set
Not set
Not set
Not set
Not set
Not set
Not set
Not set
SINAMICS G130/G150
FP
-
-
-
-
-
-
-
-
-
-
-