2 Parameters
2.2 List of parameters
The monitoring time must be extended if the faults that occur cannot be immediately and successfully acknowledged
(e.g. for faults that are permanently present).
In the case of p1210 = 14, 16, the faults which are present must be acknowledged manually within the time in
p1213[0]. Otherwise, fault F07320 is generated after the set time.
For index 1:
The start counter (refer to r1214) is only set back to the starting value p1211 if, after successful restart, the time in
p1213[1] has expired. The delay time is not effective for fault acknowledgment without automatic restart (p1210 = 1).
After a power failure (blackout) the delay time only starts after the line supply returns and the Control Unit boots. The
start counter is set to p1211, if F07320 occurred, the switch-on command is withdrawn and the fault is acknowledged.
The start counter is immediately updated if the starting value p1211 or the mode p1210 is changed.
p1213[0...1]
Automatic restart monitoring time / AR t_monit
B_INF
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
0.0 [s]
Description:
Sets the monitoring time of the automatic restart (AR).
Index:
[0] = Restart
[1] = Reset start counter
Dependency:
Refer to: p1210, r1214
Notice:
A change is only accepted and made in the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
After fault F07320 occurs, the switch-on command must be withdrawn and all of the faults acknowledged so that the
automatic restart function is re-activated.
Note:
For index 0:
The monitoring time starts when the faults are detected. If the automatic acknowledgments are not successful, the
monitoring time runs again. If the drive has not restarted at the end of the monitoring time, fault F07320 is signaled.
The monitoring is deactivated with p1213 = 0. If p1213 is set to a value which is lower than in p1212, fault F07320 is
generated at each restart. If, for p1210 = 1, the time in p1213 is set lower than in p1212, then fault F07320 is also
generated at each restart.
The monitoring time must be extended if the faults that occur cannot be immediately and successfully acknowledged
(e.g. for faults that are permanently present).
For index 1:
The start counter (refer to r1214) is only set back to the starting value p1211 if, after successful restart, the time in
p1213[1] has expired. The delay time is not effective for fault acknowledgment without automatic restart (p1210 = 1).
After a power failure (blackout) the delay time only starts after the line supply returns and the Control Unit boots. The
start counter is set to p1211, if F07320 occurred, the switch-on command is withdrawn and the fault is acknowledged.
The start counter is immediately updated if the starting value p1211 or the mode p1210 is changed.
r1214.0...15
CO/BO: Automatic restart status / AR status
VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Functions
Not for motor type: -
Min
-
Description:
Displays the status of the automatic restart (AR).
Bit field:
Bit
00
01
02
03
04
05
06
07
342
Signal name
Initialization
Wait for alarm
Auto restart act
Setting the acknowledgment command
Acknowledge alarms
Restart
Delay time running after automatic switch-
on
Fault
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
10000.0 [s]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.0 [s]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
SINAMICS G130/G150