Siemens G130 List Manual page 323

Hide thumbs Also See for G130:
Table of Contents

Advertisement

r1099.0
CO/BO: Skip band status word / Skip band ZSW
VECTOR_G
Can be changed: -
Data type: Unsigned32
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Display and BICO output for the skip bands.
Bit field:
Bit
00
Dependency:
Refer to: r1170
Note:
For bit 00:
With the bit set, the setpoint speed is within the skip band after the ramp-function generator (r1170).
The signal can be used to switch over the drive data set (DDS).
p1101[0...n]
Skip speed bandwidth / n_skip bandwidth
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
0.000 [rpm]
Description:
Sets the bandwidth for the skip speeds/velocities 1 to 4.
Dependency:
Refer to: p1091, p1092, p1093, p1094
Note:
The setpoint (reference) speeds are skipped (suppressed) in the range of the skip speed +/-p1101.
Steady-state operation is not possible in the skipped (suppressed) speed range. The skip (suppression) range is
skipped.
Example:
p1091 = 600 and p1101 = 20
--> setpoint speeds between 580 and 620 [rpm] are skipped.
For the skip bandwidths, the following hysteresis behavior applies:
For a setpoint speed coming from below, the following applies:
r1170 < 580 [rpm] and 580 [rpm] <= r1114 <= 620 [rpm] --> r1119 = 580 [rpm]
For a setpoint speed coming from above, the following applies:
r1170 > 620 [rpm] and 580 [rpm] <= r1114 <= 620 [rpm] --> r1119 = 620 [rpm]
p1106[0...n]
CI: Minimum speed signal source / n_min s_src
VECTOR_G
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for lowest possible motor speed.
Dependency:
Refer to: p1080
Notice:
The effective minimum speed is formed from p1080 and p1106.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
r1170 within the skip band
alculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Calculated: -
Dyn. index: DDS, p0180
Unit group: 3_1
Scaling: p2000
Max
210000.000 [rpm]
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: p2000
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
Access level: 3
Func. diagram: 3050
Unit selection: p0505
Expert list: 1
Factory setting
0.000 [rpm]
Access level: 3
Func. diagram: 3050
Unit selection: -
Expert list: 1
Factory setting
0
FP
3050
323